Shijiazhuang High & Middle Pressure Valves Manufacturer
Home About Products Services Contact

  • By Series:

Hydraulic emergency shut-off valve QDY421F-25/40

Product Features

1. Suitable for gas or liquid ammonia pipeline, a safety protection.When the pipeline leak occurs, use hand pump unloading, realizing remote control valve is closed.When a fire, high temperature melted the fusible plug, the valve automatically shut down.
2. On the principle of the check valve, one-way only cut off, the flow direction of medium when installation must be consistent with the body logo.
3. The state of delivery, the valve normally closed.Through the hand pump on the hydraulic cylinder, the valve opens.
4. Easy operation, the valve closed check fast.

Technical parameters

Technical parameters

 

Nominal pressure MPa 2.5 4.0
Shell test pressure MPa 3.75 6.0
Seal test pressure MPa 2.75 4.4
Suitable temperature - 40ºC ~ + 150ºC
Applicable medium Ammonia, ammonia, vinyl chloride, refrigerant, etc
The standard of the flange GB/T9113-2000
Manufacturing standards JB/T9092-1999
Emergency cut-off time 10 ~ 30 seconds or less
Fusible plug melting temperature 75 + / - 5ºC
Oil cylinder suitable medium Synthesis of spindle oil, transformer oil
Oil cylinder pressure MPa 4.0 ~ 6.0

Main components:

 

The valve body The valve stem The disc spring gasket Oil cylinder Sealing ring
WCB¡¢LCB 20Cr13 20Cr13 20CrVA,1Cr18NI9 PTFE 20 ' NBR

Standing with a hydraulic emergency cut-off valve QDY421F nominal pressure PN2.5 MPa overall dimensions

 

DN L D D1 D2 D3 convex D4 convex b f Z - H
25 160 115 85 65 57 58 16 4 4-14 262
32 180 140 100 76 65 66 18 4 4 - phi 18 245
40 200 150 110 84 75 76 18 4 4 - phi 18 321
50 230 165 125 99 87 88 20 4 4 - phi 18 346
80 310 200 160 132 120 121 24 4 8 - phi 18 435
100 350 235 190 156 149 150 24 4.5 8-22 460