Shijiazhuang High & Middle Pressure Valves Manufacturer
Home About Products Services Contact

  • By Series:

Hydraulic emergency shut-off valve QDY421F-25/40

Product Features

1. Suitable for gas or liquid ammonia pipeline, a safety protection.When the pipeline leak occurs, use hand pump unloading, realizing remote control valve is closed.When a fire, high temperature melted the fusible plug, the valve automatically shut down.
2. On the principle of the check valve, one-way only cut off, the flow direction of medium when installation must be consistent with the body logo.
3. The state of delivery, the valve normally closed.Through the hand pump on the hydraulic cylinder, the valve opens.
4. Easy operation, the valve closed check fast.

Technical parameters

Technical parameters:

 

Nominal pressure MPa 2.5 4.0
Shell test pressure MPa 3.75 6.0
Seal test pressure MPa 2.75 4.4
Suitable temperature - 40ºC ~ + 150ºC
Applicable medium Ammonia, ammonia, vinyl chloride, refrigerant, etc
The standard of the flange GB/T9113-2000
Manufacturing standards JB/T9092-1999
Emergency cut-off time 10 ~ 30 seconds or less
Fusible plug melting temperature 75 + / - 5ºC
Oil cylinder suitable medium Synthesis of spindle oil, transformer oil
Oil cylinder pressure MPa 4.0 ~ 6.0

Main components:

 

The valve body The valve stem The disc spring gasket Oil cylinder Sealing ring
WCB 20Cr13 20Cr13 20CrVA,1Cr18NI9 PTFE 20 ' NBR

Hydraulic emergency cut-off valve QDY421F - 25 nominal pressure PN2.5 MPa shape size and the connection size

 

DN L D D1 D2 D3 convex D4 concave b f Z - H1 H2
150 444 300 250 211 203 204 28 4.5 8 - phi 26 590 353
200 533 360 310 274 259 260 30 4.5 12 - phi 26 695 410
250 622 425 370 330 312 313 32 4.5 12-30 735 441

Our strength